124
ID
Message (pri-
ority)
1. Cause
2. Measures
Access right
D4
Control high
pressure ("i")
1. Air in the heating circuit; secondary or
heating circuit pump blocked; con-
denser contaminated; pressure sensor
faulty
2. Vent heating circuit; check secondary
and heating circuit pump; flush heating
circuit; check system pressure
Contractor
D6
Flow switch
("
U
")
1. The flow switch has responded; inade-
quate throughput
2. Check primary pumps and circulation
pump for brine/primary circuit. For
type WW/WWC check filter and inter-
mediate circuit heat exchanger; check
primary circuit pressure
Customer
E1
Ext. Heat gen-
eration ("
U
")
1. Fault on the external heat source
2. Check external heat source
Customer
E2
Fault, lag heat
pump ("
U
")
1. Fault at the lag heat pump in a cascade
2. Check the lag heat pump display
Customer
FF
New start ("i")
1. Control unit restart
2. No measures required
Customer
Heat pump characteristics in case of messages
All messages have a 2-digit number as identifier, the so-called "ID". This number
corresponds to the ID in the table above "Message display" from page 114.
ID
Characteristics and effects of system/control unit
10
18
Outside temperature is assumed to be -40 °C.
20
28
The temperature value of the secondary
return
sensor plus 5 K is selected.
The heat pump is stopped (message A9) if the secondary flow and return
temperature sensors are faulty.
21
29
The temperature value of the secondary
flow
sensor plus 5 K is selected.
The heat pump is stopped (message A9) if the secondary flow and return
temperature sensors are faulty.
30
31
38
39
The heat pump will not start.
Troubleshooting
Control unit diagnostics
(cont.)