Danger
DHW with
temperatures in
excess of 60 ºC
can cause
scalding.
To limit the temperature to 60 °C,
install a mixing device, e.g. an
automatic thermostatic mixing
valve (DHW cylinder accessory).
Access
■ "
Device settings
"
■ "
Programming
"
■ "
DHW
"
■
y
to
"Max. temp."
■
T
or
U
Standard setting
60 °C
Setting range
20 to 80 °C
Hysteresis/Hysteresis booster heater
Parameter
■ 6007
Hysteresis
Relative to heating by heat pump.
Parameter
■ 6008
Hysteresis booster heater
Relative to heating with an instantane-
ous water heater, an external heat
source or an electric immersion heater
EHE (DHW cylinder accessories).
These settings determine the deviation
from the set DHW cylinder temperature
("
DHW cylinder temp.
") at which the
cylinder heating is switched on and off by
the heat pump ("
Hysteresis
").
If an additional booster heater is also
installed, the "
Hyst. booster heater
"
parameter is also relevant.
DHW control settings
Max. temperature
(cont.)