166
A specific outside temperature can be
assigned to a certain cooling circuit flow
temperature using the "
Cooling curve
level
" and "
slope
" parameters.
■ The "
Cooling curve level
" parameter
moves the cooling curve along the flow
temperature axis.
■ The "
Cooling curve slope
" parame-
ter assigns a lower flow temperature to
the same outside temperature if there
is a greater slope.
+
_
A
Flow temperature
B
Outside temperature
C
Cooling curve
D
Cooling curve with a higher level
(
C
offset)
E
Cooling curve with a greater slope
Access
■ "
Device settings
"
■ "
Programming
"
■ "
Cooling
"
■
y
to "
Cooling curve level
"
or
■
y
to "
Cooling curve slope
"
■
?
to display the diagrams
Cooling curve level
Standard setting
0
Setting range
-15 to 40
Slope, cooling curve
Standard setting
1,2
Setting range
0 to 3,5
Cooling control settings
Cooling curve level/slope
(cont.)
5368 522 UAE