133
C
Selected value "
Temp. diff. cool-
ing
"
D
Adjusted outside temperature
E
Cooling function ON
F
Cooling function OFF
Access
■ "
Device settings
"
■ "
Programming
"
■ "
System definition
"
■
y
to
"Temp. diff. cooling"
■
5
or
%
Standard setting
4,0 K
Setting range
1,0 to 20,0 K
Swimming pool
Parameter
■ 7008
Specify whether a swimming pool is con-
nected and heated.
Note
Initially set parameter "External exten-
sion" (7010) to "Yes" (see page 135). If
that has not been done, then parameter
"Swimming pool" will not be displayed.
Access
■ "
Device settings
"
■ "
Programming
"
■ "
System definition
"
■
y
to
"Swimming pool"
■
"YES"
or
"NO"
Standard setting
No
Setting range
Yes/No
Cascade control (lead appliance)
Parameter
■ 700A
Set whether the heat pump operates as
lead appliance in a cascade comprising
several heat pumps.
Access
■ "
Device settings
"
■ "
Programming
"
■ "
System definition
"
■
y
to
"Cascade control"
■
l
or
m
Standard setting
0
Setting range
0 to 2
Explanation:
0 No cascade
1 Cascade control via "External exten-
sion H1"
2 No function
System definition control settings
Temperature differential cooling
(cont.)
5368 522 UAE