75
Equipment
Connection
Comments
ID
Setting parameters (group)
Frost protection
monitor and brine
pressure limiter
1X3.8
1X3.9
(see page 24
and 37)
When using type BW in conjunction
with the AC-Box (accessory), the brine
pressure limiter is connected in series
with the frost protection monitor of the
AC-Box (remove jumper)
No parameters need to be set
Primary pump and
well pump (acces-
sory) in the primary
circuit (max. 200 W)
See the following
illustration
■ Type BW
Ó
WW
Connect both pumps via terminal
2X8.5
■ Type BWC
Ó
WWC
Control all primary pumps already
installed and connected to terminal
2X8.5 together with the on-site well
pump via terminal 2X8.5
No parameters need to be set
M
1~
?
1x1.
?
2x8.5
1x2.N
A B
M
3~
D
E
L1L2 L3
I>I>I>
C
?
A
Terminals at PCB 1 and 2
B
Primary pump (max. 200 W, already
integrated and connected for type
BWC/WWC)
C
Contactor relay (on site)
D
Protective motor switch (on site)
E
Well pump
Installation sequence
Positioning of all terminals
(cont.)
5368 522 UAE
Installation