117
ID
Message (pri-
ority)
1. Cause
2. Measures
Access right
52
DHW sens.
Bottom ("
U
")
1. Short circuit, DHW temperature sensor,
bottom
2. Check the sensor and replace, if
required
Customer
54
DHW solar
("
U
")
1. Short circuit, DHW temperature sensor
solar - Vitosolic
2. Check the sensor and replace, if
required
(see Vitosolic installation instructions)
Customer
58
DHW sens. Top
("
U
")
1. Break, DHW temperature sensor, top
2. Check the sensor and replace, if
required
Customer
5A
DHW sens.
Bottom ("
U
")
1. Break, DHW temperature sensor, bot-
tom
2. Check the sensor and replace, if
required
Customer
5C
DHW solar
("
U
")
1. DHW temperature sensor solar - Vito-
solic
2. Check the sensor and replace, if
required
(see Vitosolic installation instructions)
Customer
60
Buffer cyl.sen-
sor ("
U
")
1. Short circuit, heating water buffer cyl-
inder temperature sensor
2. Check the sensor and replace, if
required
Customer
63
Ext. Heat
source ("
U
")
1. Short circuit, external heat source tem-
perature sensor
2. Check the sensor and replace, if
required
Customer
68
Buffer cyl.sen-
sor ("
U
")
1. Break, heating water buffer cylinder
temperature sensor
2. Check the sensor and replace, if
required
Customer
6B
Ext. Heat
source ("
U
")
1. Break, external heat source tempera-
ture sensor
2. Check the sensor and replace, if
required
Customer