Setting parameters
Setting range
Standard
setting
Commission-
ing
Temp. sensor 2
Yes/No
No
Booster heater
Yes/No
No
DHW with electric
power
Yes/No
Yes
Electric heating
Instantaneous heating
water heater
Yes/No
No
Electric heating
Yes/No
Yes
Max. stage, electric
booster heater
1 to 3
3
Stage for power-OFF
0 to 3
0
Hydraulic
Heat pump for drying
buildings
Yes/No
No
Screed program
0 to 12
0
Set flow temperature,
external demand
0 to 70 °C
50 °C
Heating water buffer cylinder
Buffer cylinder
No/Yes
No
Switching times, buffer
cylinder
0 to 3
2
Fixed temperature
1 to 70 °C
50 °C
Hysteresis
2 to 20 K
5 K
Max. temperature
1 to 70 °C
60 °C
Heating circuits
Room temperature,
standard
10 to 30 °C
20 °C
Room temperature,
reduced
10 to 30 °C
16 °C
Switching times, heating
circuit
0 to 3
2
Activating the remote
control
Yes/No
No
Heating curve level
-15 to 40
0
Heating curve slope
0 to 3,5
0,6
Commissioning/service reports
Control parameter report
(cont.)