175
Function
Explanation
Connection
Auxiliary output with switch-
ing times (e.g. DHW circu-
lation pump)
■ Pmax.=150 W
■ Observe the information regarding
the total current drawn (from the
table)!
■ U=230 V
2X7.11
Central fault message
Zero volt contact:
■ closed=fault
■ open=no fault
■ Contact breaking capacity 250 V~,
4(2) A
■ unsuitable for safety LV
2X7.12
2X7.13
Function components 230 V on PCB 2 (motherboard, terminal strip X8)
Function
Explanation
Connection
End of safety chain
■ 'Live' in case of fault-free safety chain 2X8.1
Compressor control via
controller of the electronic
expansion valve (EEV)
■ Control internal contact between
2X8.1 and 2X8.2 is closed in case of
heat demand.
■ 2X8.2 is 'live'
■ If the compressor fails to operate, the
enable signals from the EEV control-
ler via a suitable relay to the EEV PCB
may be missing.
2X8.2
N/A
N/A
2X8.3
2X8.4
Primary pump, well pump
control
■ Pmax.=200 W
■ Observe the information regarding
the total current drawn (from the
table)!
2X8.5
Natural cooling control
■ Observe the information regarding
the total current drawn (from the
table)!
■ This control signals is additionally
required with the AC-Box.
2X8.6
Connection and wiring diagrams
PCB 2: Function components 230 V
(cont.)
5368 522 UAE
Service