88
Location of connections and cable entries
D
C
B
A
F
E
Lower entry area
F
for 1 to 3 power cables. Cable length approx. 1.50 m plus wall
clearance.
1.
Remove the front, top and side panel
(see page 57).
2.
Remove contact shield
C
from
mains terminals
A
and
B
.
3.
Fit cable fittings (in the pack) to the
entries
F
in the back panel.
4.
Guide the power cables through the
cable fittings from the back into the
appliance (see page 11) and apply
strain relief.
Installation sequence
Power supply
(cont.)
5368 522 UAE