204
Components
Connec-
tion
Connected
load [W]
Voltage [V] max. break-
ing capacity
[A]
Actuation of external heat
source
2X7.1
2X7.2
zero volt
contact
250
*
7
4(2)
Central fault message
2X7.12
2X7.13
zero volt
contact
*
7
250
4(2)
Total current
max. 5(3) A
Vitocal 300-G
Typ
e
106
108
110
112
114
116
Output details
heat pump type
BW/BWC
*
8
Heat pump mod-
ule
Typ
e
300/10
6
300/10
8
300/11
0 300/112
300/11
4
300/11
6
Rated output
kW
6,2
8,4
10,2
12,1
15,1
17,6
Refrigerating
capacity
kW
4,9
6,7
8,1
9,6
12,0
13,8
Power consump-
tion
kW
1,38
1,82
2,23
2,57
3,27
3,99
Coefficient of Per-
formance
∊
(COP)
during heating
operation
4,5
4,6
4,6
4,7
4,6
4,4
Output details
heat pump type
WW/WWC
*
9
Heat pump mod-
ule
Typ
e
300/10
6
300/10
8
300/11
0 300/112
300/11
4
300/11
6
Rated output
kW
8,0
11,0
13,6
15,8
19,8
21,6
Refrigerating
capacity
kW
6,7
9,2
11,6
13,3
16,6
17,9
Power consump-
tion
kW
1,4
2,0
2,3
2,8
3,3
4,3
*
7
Unsuitable for voltages below 42 V
*
8
At operating point B0/W35 to DIN EN 14511: B0 = Brine inlet temperature 0 °C / W 35 = Heating water
flow temperature 35 °C.
*
9
At operating point W10/W35 to DIN EN 14511:W10 = Primary source temperature 10 °C / W 35 = Heating
water flow temperature 35 °C.
Specification
Specification
(cont.)
5368 522 UAE