140
Parameter
■ 7017
Specify whether a Vitocom 100 is instal-
led in the system.
Access
■ "
Device settings
"
■ "
Programming
"
■ "
System definition
"
■
y
to
"Vitocom 100"
■
"YES"
or
"NO"
Standard setting
No
Setting range
Yes/No
External blocking effect
Parameter
■ 701A
Details at what setting parameter "Ext.
Blocking" which system component will
be blocked.
Any combination of individual compo-
nents is possible.
Yes
means that this component is
blocked.
Access
■ "
Device settings
"
■ "
Programming
"
■ "
System definition
"
■
y
to
"Ext. blocking effect"
■
l
or
m
Standard setting
0
Setting range
0 - 31
Value Secondary
pump/com-
pressor
blocked
Cylinder
pump
blocked
Heating cir-
cuit pump
M3 blocked
Heating cir-
cuit pump
M2 blocked
Heating cir-
cuit pump
A1 blocked
0
1
x
2
x
3
x
x
4
x
5
x
x
6
x
x
7
x
x
x
System definition control settings
Vitocom 100
5368 522 UAE