Observe parameter 5735 (number of
external heat pumps).
Cascade control (lag appliance)
Parameter
■ 700A
■ 7000
Setting for the lag heat pumps in a cas-
cade.
Access
■ "
Device settings
"
■ "
Programming
"
■ "
System definition
"
■
y
to
"Cascade control"
■
l
or
m
Setting
■ 700A
Ó
0
■ 7000
Ó
11
Output lag heat pump
Parameter
■ 700B
Entry of the output of the lag heat
pump(s) as average value of all lag appli-
ances.
Entry only in the lead appliance.
Example:
Lag heat pump 1 = 10 kW
Lag heat pump 2 = 14 kW
Average value
= 12 kW (set value)
Access
■ "
Device settings
"
■ "
Programming
"
■ "
System definition
"
■
y
to
"Output lag heat pump"
■
l
or
m
Standard setting
10 kW
Setting range
0 to 255 kW
Note
Observe parameter 5735 (number of
external heat pumps).
System definition control settings
Cascade control (lead appliance)
(cont.)