68
Equipment
Connection
Comments
ID
Setting parameters (group)
Circulation pump for
cylinder reheating
2X8.13
1X2.N
100 W, control only via on-site contac-
tor; no simultaneous operation with
immersion heater EHE
7B00 Ext. heat source
Ó
Yes (ext. heat source)
7B0D Ext. HS for DHW
Ó
Yes (ext. heat source)
Additional components
Equipment
Connection
Comments
ID
Setting parameters (group)
Mixer motor, heating
circuit M2
2X8.9
V
OPEN
1X1.
?
1X2.N
2X8.10
v
CLOSE
Heating circuit M2 with directly control-
led mixer without KM BUS
By selecting the system dia-
grams
Extension kit for
heating circuit with
mixer M3 via KM
BUS
3X1.25
Ó
1
aVG
3X2.25
Ó
2
aVG
Component terminals, see installation
instructions, extension kit; observe
heating circuit allocation via DIP
switch
By selecting the system dia-
grams
Vitotrol 200 remote
control
3X1.25
Ó
1
aVG
3X2.25
Ó
2
aVG
See Vitotrol installation instructions;
observe heating circuit allocation via
DIP switch
2003
Ó
Yes (heating circuit A1)
3003
Ó
Yes (heating circuit M2)
4003
Ó
Yes (heating circuit M3)
External exten-
sion H1
3X1.25
Ó
1
aVG
3X2.25
Ó
2
aVG
See separate installation instructions
(connection to KM BUS)
7010 External extension
Ó
Yes (system configuration)
Vitocom 100
3X1.25
Ó
1
aVG
3X2.25
Ó
2
aVG
KM BUS control
7017 Vitocom
Ó
Yes (system configuration)
Vitosolic 100
3X1.25
Ó
7
3X2.25
Ó
8
Connection to terminal 7 and 8 of the
Vitosolic 100, KM BUS control; see
Vitosolic installation instructions
7016 Type Vitosolic
Ó
1 (system configuration)
Installation sequence
Positioning of all terminals
(cont.)
5368 522 UAE