131
Parameter
■ 7000
Select the system diagram during com-
missioning.
This selection automatically enables and
monitors all components associated with
the respective scheme.
Access
■ "
Device settings
"
■ "
Programming
"
■ "
System definition
"
■
"System diagram"
■
l
or
m
Standard setting
2
Setting range
0 to 11
Note
For further information, see page 13.
Language selection
Parameter
■ 7001
Operating instructions
Temperature differential heating
Parameter
■ 7003
The heating limit temperature defines
the value of the outside temperature,
below which central heating commen-
ces.
The heating limit temperature is the
result of the selected set room tempera-
ture less the value entered under "
Temp.
diff. heating
".
Example:
The selected set room temperature is
20 °C; the temperature entered under
"
Temp. diff. heating
" is 4,0 K.
Central heating commences if the adjus-
ted outside temperature drops below
16 °C (heating limit temperature).
If the adjusted outside temperature
exceeds 18 °C, central heating stops
(because of the specified hysteresis of
2 K).
System definition control settings
System diagram
5368 522 UAE
Service