118
ID
Message (pri-
ority)
1. Cause
2. Measures
Access right
70
Room tempera-
ture sensor
HK1 ("
U
")
1. Short circuit, room temperature sensor,
heating circuit 1
2. Check the sensor and replace, if
required
(see Vitotrol installation instructions)
Customer
71
Room tempera-
ture sensor
HK2 ("
U
")
1. Short circuit, room temperature sensor,
heating circuit 2
2. Check the sensor and replace, if
required
(see Vitotrol installation instructions)
Customer
72
Room tempera-
ture sensor
HK3 ("
U
")
1. Short circuit, room temperature sensor,
heating circuit 3
2. Check the sensor and replace, if
required
(see Vitotrol installation instructions)
Customer
73
Room tempera-
ture sensor NC
("
U
")
1. Short circuit, room temperature sensor
NC
2. Check the sensor and replace, if
required
Customer
78
Room tempera-
ture sensor
HK1 ("
U
")
1. Break, room temperature sensor, heat-
ing circuit 1
2. Check the sensor and replace, if
required
(see Vitotrol installation instructions)
Customer
79
Room tempera-
ture sensor
HK2 ("
U
")
1. Break, room temperature sensor, heat-
ing circuit 2
2. Check the sensor and replace, if
required
(see Vitotrol installation instructions)
Customer
7A
Room tempera-
ture sensor
HK3 ("
U
")
1. Break, room temperature sensor, heat-
ing circuit 3
2. Check the sensor and replace, if
required
(see Vitotrol installation instructions)
Customer
7B
Room tempera-
ture sensor NC
("
U
")
1. Break, room temperature sensor natu-
ral cooling
2. Check the sensor and replace, if
required
Customer
Troubleshooting
Control unit diagnostics
(cont.)
5368 522 UAE