Telephone Button Programming
500 Series Programs
13-76
Strata CTX Programming - Part 3:Telephone Button Programming 04/03
508
Door Lock Control
Assignment
,
+ROG
This assignment is used to configure up to 10 door lock control relays.
The contacts of these relays are used to control electrical door locks.
One door lock relay can be assigned to each of the eight Door Phone
Control Boxes (DDCB, Port B) and/or one to each of the two BIOU
PCBs (any one of the four control relays).
Note
If a door lock is assigned to a DDCB, the second jack (Port B)
will provide the door lock relay contacts. This jack can not be
used to connect an MDFB door phone.
508-00
Door Lock Number
n,
+ROG
n =
1~4 (CTX100)
1~5 (CTX670 Basic)
1~10 (CTX670 Exp.)
Enter the door lock control number to configure.
508-01
Interface Type
)%
, n,
+ROG
n =
1.
None (default)
2.
BIOU
3.
DDCB
Enter the system Page Group number that should ring for the
selected tenant when a door phone button is pressed during the
system Night Mode.
508-02
BIOU Relay Number
)%
, n,
+ROG
n =
0~8 (default = 0)
•
BIOU1 provides control
relays 1~4
•
BIOU2 provides control
relays 5~8.
Assign BIOU control relay as a Door Lock Relay. This relay activates
when the Door Lock button is pressed or a Door Lock access code is
dialed.
Note
The CTX100 ACTU built-in relay is programmed as relay 5.
For this relay operation BIOU2 is installed as default in a
virtual equipment position Cabinet 2, Slot 5, PCB code 20, in
Program 100. To install an actual BIOU2 and disable the
ACTU built-in relay, use the programming telephone to
remove the virtual BIOU2 and then install the actual BIOU2 in
Cabinet 01/slot 01~08 in the normal manner. BIOU relay
functions are assigned in
“Program 515” on page 13-78
. This
field is required if you selected BIOU in 01 Interface Type
above.
508-03
DDCB Equipment No.
)%
, n,
+ROG
,
+ROG
n =
Cabinet 01 (CTX100),
01~02 (CTX670 Basic),
01~07 (CTX670 Exp.)
Slot 01~8 (CTX100),
01~10 (CTX670)
Circuit 01~16
Enter the DDCB equipment number to which the Door Lock should be
assigned. This is the cabinet, slot, and circuit number of the ADKU,
BDKU/BDKS or PDKU interface PCB to which the the DDCB is to be
connected.
Enter data as XXYYZZ:
XX=cabinet 01~07; YY=slot 01~10; ZZ=circuit 01~16
Example: If the DDCB interface should be connected to a ADKU,
PDKU or BDKU/BDKS in cabinet shelf 5, slot 2, circuit 3, enter
050203.
Note
If a PDN is assigned to the DDCB equipment number it must
be deleted, using PRG201, before attempting to assign the
DDCB console.
Cabinet numbers:
•
CTX100: Select 01 for Base and Expansion cabinet.
•
CTX670: Select 01 for Base and 02~07 respectively for each
Expansion cabinet.
Slot numbers:
•
CTX100: Select 01~04 for Base slots and 05~08 for Expansion
slots.
•
CTX670: Select 01~08 for Base slots and 01~10 for Expansion
slots.
509
DR Override by
System Speed Dial
,
+ROG
This command assigns the COS, DRL, FRL and QPL values used by
DR Override by Speed Dial.
509-01
Override COS
)%
, n,
+ROG
n =
1~32
(default =1)
Select the override COS value.
509-02
Override DRL
)%
, n,
+ROG
n =
1~16
(default =1)
Select the override DRL value.
Programs 500~577
(continued)
Button
Sequence
Value(s)
Summary