RemotEye III User Manual – 62330-005
Registers Data Type
Size
Description
Units
Comments
Point
10088
Discrete
1-Bit
EMD Humidity is at High Critical
Point
True/False (1/0)
10089
Discrete
1-Bit
EMD Humidity at Low Warning Point
True/False (1/0)
10090
Discrete
1-Bit
EMD Humidity at High Warning
Point
True/False (1/0)
10091
Discrete
1-Bit
EMD Temperature at Low Critical
Point
True/False (1/0)
10092
Discrete
1-Bit
EMD Temperature at High Critical
Point
True/False (1/0)
10093
Discrete
1-Bit
EMD Temperature at Low Warning
Point
True/False (1/0)
10094
Discrete
1-Bit
EMD Temperature at High Warning
Point
True/False (1/0)
In
for
m
at
ion
al
10095
Discrete
1-Bit
Input Power Failure
True/False (1/0)
10096
Discrete
1-Bit
EPO has Tripped
True/False (1/0)
10100
Discrete
1-Bit
UPS is Waiting at a Specified Time by
User before Start-up
True/False (1/0)
10101
Discrete
1-Bit
Remote Switch Control Enabled
True/False (1/0)
10102
Discrete
1-Bit
Auto Re-Transfer Enabled
True/False (1/0)
10103
Discrete
1-Bit
Manual Mode Selected
True/False (1/0)
10104
Discrete
1-Bit
UPS has Immediately switch to
inverter at startup
True/False (1/0)
10105
Discrete
1-Bit
UPS has been forced to Bypass
True/False (1/0)
10106
Discrete
1-Bit
Local Run Command Issued
True/False (1/0)
10107
Discrete
1-Bit
Remote Run Command Issued
True/False (1/0)
10108
Discrete
1-Bit
Firmware has been Updated
True/False (1/0)
10113
N/A
N/A
N/A
N/A
10114
Discrete
1-Bit
UPS Output is Off
True/False (1/0)