UPS Shutdown Events (Applicable to 1600XP only)
This page allows the administrator to modify the output shutdown parameters of the UPS that depends on the event.
UPS Output Shutdown Delay (secs)
This field allows the administrator to configure or view the delay (in seconds) of the UPS switching from the Run
(Inverter) mode to the Output Shutdown mode after receiving the Output Shutdown command.
The “UPS output shutdown delay” time count down will be synchronized with the output shutdown delay time
setting in the Toshiba RemotEye Client Shutdown Software program for all connected clients (See page 103
Toshiba RemotEye Client Software for more information). To avoid improper shutdown of the clients, the “UPS
output shutdown delay” time setting in the RemotEye III should always be greater than the Toshiba RemotEye
Client Shutdown Software Service program's shutdown delay setting.
UPS Event
This field column shows the event attributed to a shutdown action.
•
Input Power Failure
– This field shows the action taken upon detection of an input power failure. Default:
Client Warning
•
Battery Low
– This field shows the action taken upon detection of a battery low condition.
•
Default: Client Warning
•
UPS Overload
– This field shows the action taken upon detection of a UPS Overload condition:
•
Default: Client Warning
•
UPS System Overheat
– This field shows the action taken upon detection of a UPS over temperature
condition.
•
Default: Client Warning
•
EMD Temperature Over Threshold
– This field shows action taken upon detection of a EMD
Temperature Over Threshold condition.
•
Default: Disabled.
•
EMD Alarm-1
- This field shows action taken upon detection of a EMD Alarm-1 condition.
•
Default: Disabled
.
•
EMD Alarm-2
– This field shows action taken upon detection of a EMD Alarm-2 condition.
•
Default: Disabled
.
•
Recurring On/Off Schedule
– This field shows the programmed Recurring On/Off Schedule setting.
Default: Disabled.
•
Non-Recurring On/Off Schedule
– This field shows the programmed Non-Recurring On/Off Schedule
setting.
•
Default: Disabled
.
Action
This field allows the administrator to set a course of action to be taken in the event of a fault that are listed in the
“UPS Event” column.
Disable - Action is disabled; no action will be taken.
Client Warning - A warning message will be broadcasted to the connected clients. Note: The Toshiba RemoteEye
Client Shutdown Software has to be installed on the client.
Client Shutdown - A warning message will be broadcasted and the shutdown command will be sent to the connected
clients. Note: The Toshiba RemoteEye Client Shutdown Software has to be installed on the client.
UPS Output Shutdown - A warning message will be broadcasted and the shutdown command will be sent to the
connected clients, and the UPS output will be shutdown.