RemotEye III User Manual – 62330-005
161
Modbus Input Coil for 4200FA/4300: ALARMS and STATUS
NOTE: Items Lined out (e.g. Lined Out) are not supported at this time.
Registers Data Type
Size
Description
Units
Comments
R
MT
I-
3
St
a
tus
10001
Discrete
1-Bit
RemotEye III Data Link
True/False (1/0)
0 = Link Up; 1 = Link Down
10002
Discrete
1-Bit
RemotEye III Network Link
True/False (1/0)
0 = Link Up; 1 = Link Down
U
P
S M
o
de
10003
N/A
N/A
N/A
N/A
10004
Discrete
1-Bit
Online Mode
True/False (1/0)
10005
Discrete
1-Bit
Backup Mode
True/False (1/0)
10006
Discrete
1-Bit
Bypass Mode
True/False (1/0)
10007
Discrete
1-Bit
Shutdown Mode
True/False (1/0)
10008
N/A
N/A
N/A
N/A
B
a
tte
ry
S
ta
tu
s
10009
Discrete
1-Bit
UPS Battery Status Unknown
True/False (1/0)
10010
Discrete
1-Bit
UPS Battery Status Normal
True/False (1/0)
10011
Discrete
1-Bit
UPS Battery Status Low
True/False (1/0)
10012
Discrete
1-Bit
UPS Battery Status Depleted
True/False (1/0)
10013
Discrete
1-Bit
UPS Battery Status Discharging
True/False (1/0)
10014
Discrete
1-Bit
UPS Battery Status Test Failure
True/False (1/0)
B
a
tt
ery
C
h
a
rg
e S
ta
tu
s
10015
Discrete
1-Bit
Protective Charging Set
True/False (1/0)
10016
Discrete
1-Bit
Equalized Charging Set
True/False (1/0)
10017
N/A
N/A
N/A
N/A
10018
N/A
N/A
N/A
N/A
10019
N/A
N/A
N/A
N/A
Summary of Contents for RemotEye III
Page 1: ... ...
Page 117: ...116 RemotEye III User Manual 62330 005 Figure 62 RemotEye Save Log Utility Set Page ...
Page 166: ......