RemotEye III User Manual – 62330-005
145
Registers Data Type
Size
Description
Units
Comments
E
x
tern
a
l B
a
tt
ery
C
a
b
in
et
W
/
Sma
rt
C
ha
rg
er
St
a
tus
10025
Discrete
1-Bit
Battery Cabinet 1 Enabled
True/False (1/0)
1 = Enabled; 0 = Disabled
10026
Discrete
1-Bit
Battery Cabinet 2 Enabled
True/False (1/0)
1 = Enabled; 0 = Disabled
EMD
10027
Discrete
1-Bit
EMD Enabled
True/False (1/0)
10028
Discrete
1-Bit
EMD Alarm-1
True/False (1/0)
0 = no Alarm; 1 = Alarm Triggered
10029
Discrete
1-Bit
EMD Alarm-2
True/False (1/0)
0 = no Alarm; 1 = Alarm Triggered
F
a
u
lts
10030
Discrete
1-Bit
General Alarm Fault
True/False (1/0)
1 = One or more fault reported, see below for cause; 0 = No
Faults
10031
Discrete
1-Bit
Open Fuse Fault
True/False (1/0)
10032
Discrete
1-Bit
Current Limit Fault
True/False (1/0)
10033
Discrete
1-Bit
Output Overcurrent Fault
True/False (1/0)
10034
Discrete
1-Bit
DC Bus Overcurrent Fault
True/False (1/0)
10035
Discrete
1-Bit
DC Bus Overvoltage Fault
True/False (1/0)
10036
Discrete
1-Bit
DC Bus Imbalance Fault
True/False (1/0)
10037
Discrete
1-Bit
DC Bus Under Voltage During Boost-
up Fault
True/False (1/0)
10038
Discrete
1-Bit
DC Bus Under Voltage During
Charging Fault
True/False (1/0)
10039
Discrete
1-Bit
Charger Overvoltage Fault
True/False (1/0)
10040
Discrete
1-Bit
Output Under voltage Fault
True/False (1/0)