86
RemotEye III User Manual – 62330-005
•
Record Number - Maximum number of records is 255.
•
System Input Type
•
System Output Type
•
Input Voltage
•
Output Voltage
•
Output Load
•
DC Input Voltage
•
Battery Voltage
•
Slot Location
•
Fault
4200FA/4300 Fault Records Log Format
•
Log Date – This field shows the date of the recording.
•
Log Time - This field shows the time that the values were recorded. Time is displayed in the hh:mm:ss 24-
hour format (i.e., 8:30 p.m. is 20:30:00).
•
Record Number – Maximuan number of record is 255.
•
Fault 1 – Description of fault detected.
•
Fault 2 – Description of fault detected.
Following is a table of the possible UPS fault codes and their meanings. Please refer to UPS manual for more specific
details.
Fault Code
Description
FSOPEN
Fuse opened
CL
Current limit fault occurred
DCOC
DC bus over current fault occurred
DCOV
DC bus over voltage occurred
DCIB
DC bus imbalance occurred
VOUV
Output voltage undervoltage occurred
VOOV
Output voltage overvoltage occurred
DVCOH
Device overheat occurred
BYPOL
Bypass overload occurred
CHRGOV
Charger overvoltage occurred
OOC
Output overcurrent occurred
DCUVBS
DC bus under voltage occurred at boostup UPS state
DCUVC
DC bus under voltage occurred at charging of UPS state
BYPOH
Bypass overheat occurred
INVOLRSTAOK
Inverter overload occurred and it is resettable
INVOLRSTNOK
Inverter overload occurred and it is NOT resettable
OH
UPS Overheat
DCUB
DC Imbalance
OL
UPS Overlaod
PHIRER
Phase Error
PHBRER
Bypass Phase Error
EPO
Emergency Power Off
Table 2: UPS Fault Codes
Operation Mode Records