Registers Data Type
Size
Description
Units
Comments
10112
N/A
N/A
N/A
N/A
10113
Discrete
1-Bit
UPS Output Shutdown in Progress
True/False (1/0)
10114
Discrete
1-Bit
UPS Output is Off
True/False (1/0)
10115
Discrete
1-Bit
Unsuccessful Login
(Username/Password incorrect)
True/False (1/0)
E
x
tern
a
l B
a
tt
ery
C
a
b
in
et
W
/S
m
a
rt
C
h
a
rg
er S
ta
tu
s
10116
Discrete
1-Bit
Battery Cabinet 1 String 1
Disconnected
True/False (1/0)
10117
Discrete
1-Bit
Battery Cabinet 1 String 2
Disconnected
True/False (1/0)
10118
Discrete
1-Bit
Battery Cabinet 1 String 3
Disconnected
True/False (1/0)
10119
Discrete
1-Bit
Battery Cabinet 1 String 1 Loose HCT
Connection
True/False (1/0)
10120
Discrete
1-Bit
Battery Cabinet 1 String 2 Loose HCT
Connection
True/False (1/0)
10121
Discrete
1-Bit
Battery Cabinet 1 String 3 Loose HCT
Connection
True/False (1/0)
10122
Discrete
1-Bit
Battery Cabinet 1 Over Temperature
Warning
True/False (1/0)
10123
Discrete
1-Bit
Reserved
True/False (1/0)
10124
Discrete
1-Bit
Battery Cabinet 1 Charger Over
Voltage Fault
True/False (1/0)
10125
Discrete
1-Bit
Battery Cabinet 1 Charger Over
Current Fault
True/False (1/0)
10126
Discrete
1-Bit
Battery Cabinet 1 Lost Communication True/False (1/0)
10127
Discrete
1-Bit
Battery Cabinet 2 String 1
Disconnected
True/False (1/0)
10128
Discrete
1-Bit
Battery Cabinet 2 String 2
Disconnected
True/False (1/0)
10129
Discrete
1-Bit
Battery Cabinet 2 String 3
Disconnected
True/False (1/0)
10130
Discrete
1-Bit
Battery Cabinet 2 String 1 Loose HCT
Connection
True/False (1/0)
10131
Discrete
1-Bit
Battery Cabinet 2 String 2 Loose HCT
True/False (1/0)