104
RemotEye III User Manual – 62330-005
UPS Configuration
IP Address:
Input RemotEye III IP address.
Local Configuration
This allows the administrator to set the client’s name and how it will handle a shutdown command sent by the
RemotEye III.
Client Name:
Allows the administrator to enter the client’s name or to click the “Def.” button to capture the
system’s “Computer Name”.
Shutdown Delay:
Allows the administrator to type how many seconds till the actual client system shuts down if no
script is being executed. NOTE: Make sure that the “UPS Output Shutdown Delay (secs)” under the “UPS
Management
UPS Shutdown Events” is longer than the seconds typed into this field. This will help avoid an
unwanted system shutdown format.
Force Shutdown Delay:
Allows the user to input another delay after the “Shutdown Delay” has expired. During
this time delay the tool will execute the script that has been uploaded. When the “Force Shutdown Delay” expires it
will force shutdown the client.
Script File:
The administrator can upload their script file so that it can be executed after shutdown delay time is
expired (e.g. close database).
Warn Speaker:
Allows the administrator to enable the “beep” sound alarm whenever there is a warning.
Ignore Shutdown Request:
Allows the administrator to cancel any shutdown command sent from RemotEye III.
Sleep:
Allows the administrator to send the client system to hibernate instead of shutting down. (Administrator
must first enable hibernation setting in the O.S.)
Enable POP Message:
Allows the administrator to enable or disable the POP up warning messages.
Shutdown Events
This section allows the administrator to check the boxes on which conditions should the client system to be
shutdown. When setting this make sure that these are also enabled in the RemotEye III “UPS Shutdown Events”
(UPS Management
UPS Shutdown Events, see page 69) section. These are the following conditions:
•
AC Fail
•
Battery Low
•
UPS Overload
•
UPS Over Temperature
•
Weekly and Special Day Schedule shutdown
•
EMD Temperature Over Threshold
•
EMD Alarm-1
•
EMD Alarm-2
Note: The client local shutdown delay must not be greater than the UPS shutdown delay configured in RemotEye