RemotEye III User Manual – 62330-005
111
Toshiba UPS Power Management
RemotEye III can help further protect critical load systems connected to a UPS by initiating automated shutdowns on
that equipment. RemotEye III can shutdown servers/clients upon detection of three UPS events: Input power failure,
low battery, overload. Also, RemotEye III can be used to coordinate automatic system shutdowns during weekends
or holidays. This section highlights the manners in which RemotEye III can be used in conjunction with a UPS to
manage power to UPS loads.
UPS Shutdown Events
RemotEye III can initiate output shutdown upon the occurrence of nine different UPS events Input Power Failure,
Low Battery, UPS Overload, UPS System Overheat, EMD Temperature Over Threshold, EMD Alarm-1, EMD
Alarm-2, Recurring On/Off Schedule and Non-recurring On/Off Schedule. Users can view the current setting of
these events on
UPS Shutdown Events page in UPS Management menu. To alter these settings, log in as an administrator, and
configure the UPS shutdown events action and delay times accordingly. Click the Set Value button when finished.
(See Pg. 69 for details)
Scenario:
Shutdown Event:
AC Failed
Status:
Client Shutdown
Delay (Min):
7 (default)
Warning Interval (sec):
30 (default)
UPS Output Shutdown Delay (Sec):
180 (default)
UPS Events - AC failed
22:20:00
22 : 20 : 00
22 : 27 : 00 22 : 30 : 00
Client’s local shutdown delay (Sec):
120(default)
22 : 20 : 00
22 : 27 : 00 22 : 29 : 00
INVERTER
OUTPUT
SHUTDOWN
CLIENT ON
CLIENT OFF