RemotEye III User Manual – 62330-005
163
Registers Data Type
Size
Description
Units
Comments
10046
N/A
N/A
N/A
N/A
N/A
10047
Discrete
1-Bit
Bypass Overheat Fault
True/False (1/0)
10048
Discrete
1-Bit
Output Overcurrent Fault
True/False (1/0)
10049
Discrete
1-Bit
Input Phase Rotation Error
True/False (1/0)
10050
Discrete
1-Bit
Bypass Phase Rotation Error
True/False (1/0)
W
a
rni
ng
s
10051
Discrete
1-Bit
Input Overvoltage Warning
True/False (1/0)
10052
Discrete
1-Bit
Input Under voltage Warning
True/False (1/0)
10053
N/A
N/A
N/A
N/A
10054
Discrete
1-Bit
Input MCCB Tripped Warning
True/False (1/0)
10055
Discrete
1-Bit
Bypass Overvoltage Warning
True/False (1/0)
10056
Discrete
1-Bit
Bypass Under voltage Warning
True/False (1/0)
10057
Discrete
1-Bit
Bypass Input Frequency Error
Warning
True/False (1/0)
10058
Discrete
1-Bit
Inverter Overload Warning
True/False (1/0)
10059
Discrete
1-Bit
Output Overload Warning
True/False (1/0)
10060
Discrete
1-Bit
Current Limit Warning
True/False (1/0)
10061
Discrete
1-Bit
Battery Test Failed Warning
True/False (1/0)
10062
Discrete
1-Bit
Low Battery Level Reached Warning
True/False (1/0)
10063
Discrete
1-Bit
Shutdown Battery Level Reached
Warning
True/False (1/0)
10068
Discrete
1-Bit
Battery MCCB is Off Warning
True/False (1/0)
10069
N/A
N/A
N/A
N/A
10070
Discrete
1-Bit
Charger Overvoltage Warning
True/False (1/0)
10071
N/A
N/A
N/A
N/A
10072
Discrete
1-Bit
System Test Failed Warning
True/False (1/0)
10073
Discrete
1-Bit
System Overheat Warning
True/False (1/0)
10076
N/A
N/A
N/A
N/A
10078
N/A
N/A
N/A
N/A
10079
Discrete
1-Bit
UPS and RemotEye Communication
Error Warning
True/False (1/0)
10087
Discrete
1-Bit
EMD Humidity is at Low Critical
True/False (1/0)