Registers
Data Type
Size
Description
Units
Multiplier
Comments
30146
N/A
N/A
N/A
N/A
N/A
DC B
u
s
30147
Unsigned Integer
16-Bit
DC Bus Total Voltage
Volts
X 1
30148
N/A
N/A
N/A
N/A
N/A
30149
N/A
N/A
N/A
N/A
N/A
30150
N/A
N/A
N/A
N/A
N/A
B
a
tt
ery
P
a
ra
m
et
ers
30151
Unsigned Integer
16-Bit
Battery Installation Date
Month
X 1
Month Format: MM
30152
Unsigned Integer
16-Bit
Battery Installation Date
Day
X 1
Day Format: DD
30153
Unsigned Integer
16-Bit
Battery Installation Date
Year
X 1
Year Format: YYYY
30154
N/A
N/A
N/A
N/A
N/A
30155
N/A
N/A
N/A
N/A
N/A
30156
Unsigned Integer
16-Bit
Elapsed Time on Battery Power
Seconds
X 1
30157
N/A
N/A
N/A
N/A
N/A
30158
Unsigned Integer
16-Bit
Battery Voltage
Vdc
X 1
30159
N/A
N/A
N/A
N/A
N/A
30160
Unsigned Integer
16-Bit
Battery Discharge Current
Adc
X 1
30161
N/A
N/A
N/A
N/A
N/A
30162
Unsigned Integer
16-Bit
Battery Low Detection Level
Vdc
X 1
30163
Unsigned Integer
16-Bit
Float Charge Voltage
Vdc
X 1
30164
Unsigned Integer
16-Bit
Equalize Charge Time
Hours
X 1
30165
N/A
N/A
N/A
N/A
N/A
30166
N/A
N/A
N/A
N/A
N/A
30167
N/A
N/A
N/A
N/A
N/A
30168
N/A
N/A
N/A
N/A
N/A
30169
Unsigned Integer
16-Bit
Battery Rated Ampere Hour
Ahr
X 1
30170
Unsigned Integer
16-Bit
Batteries in Series
Batteries
X 1
30171
Unsigned Integer
16-Bit
Batteries in Parallel
Batteries
X 1