Dry Contact LAN Shutdown Enable
This field shows the present mode for Dry Contact LAN Shutdown. It is set by the administrator.
0 – Disable
1 – Enable
Default Value = Enable
Dry Contact LAN Shutdown Delay (secs)
This field shows the time delay between actual event occurrence and dry contact closure. It is set by the
administrator.
Range – 0 to 800 seconds:
Dry Contact LAN Shutdown Enable
must be Enabled in order to function
Default Value = 600
Dry Contact On Battery Delay Timer (secs)
This field shows the time delay between actual event occurrence and dry contact closure. It is set by the
administrator.
Range – 0 to 800 seconds
Default Value = 10
Dry Contact Low Battery Delay Timer (secs)
This field shows the time delay between actual event occurrence and dry contact closure. It is set by the
administrator.
Range – 0 to 800 seconds
Default Value = 0