EMD (Environmental Monitoring Device)
The Environmental Monitoring Device (EMD) is a monitoring device that provides real time comprehensive remote
monitoring of environment temperature, environment humidity, and other environmental conditions via a web
browser and SNMP. The EMD also provides two users defined dry contacts for additional environmental monitoring.
These dry contacts can be used with devices that provide normally-open or normally-closed results, such as door
sensors, smoke detectors, motion detectors, and liquid detectors. The EMD is connected to the RemotEye III using an
Ethernet cable. One end, of the Ethernet cable, is connected to the RJ45 port of the EMD and the other end to the
“COM” port of the RemotEye III. Note: The EMD module is separate device which can be purchased from a Toshiba
UPS distributor.
EMD Installation
This section will explain the how to setup/install the EMD to RemotEye III.
1) Use the Cat5 (straight) cable and connect one end to the “010101” port on the EMD.
2) Now connect the other end of the Cat5 (straight) cable to the “COM” port of the RemotEye III.
3) Make sure that the “Communication Status” green LED blinks periodically. If the LED does not blink, verify that
the Cat5 cable if functional.
5) Check the “Device Status” under the “EMD Configuration” page and make sure that it is set to “Auto” (See “EMD
Configuration” on page 75).
Figure 36: EMD RemotEye III Installation
EMD Parameter