140
RemotEye III User Manual – 62330-005
Registers
Data Type
Size
Description
Units
Multiplier
Comments
30189
Signed Integer
16-Bit
Battery Cabinet 1 Ambient
Temperature
°F
x 1
30190
ASCII String
16-Bit
Battery Cabinet 2 Serial Number
UH
23XXX1
Serial #
X 1
First two character of serial number
30191
ASCII String
16-Bit
Battery Cabinet 2 Serial Number
UH
23
XXX1
Serial #
X 1
Third and fourth characters of serial
number
30192
ASCII String
16-Bit
Battery Cabinet 2 Serial Number
UH23
XX
X1
Serial #
X 1
Fifth and sixth characters of serial
number
30193
ASCII String
16-Bit
Battery Cabinet 2 Serial Number
UH23XX
X1
Serial #
X 1
Last two characters of serial number
30194
ASCII String
16-Bit
Battery Cabinet 2 Firmware Version
ex.
00
0015
FW Ver.
X 1
First two characters of Firmware
Version
30195
ASCII String
16-Bit
Battery Cabinet 2 Firmware Version
ex. 00
00
15
FW Ver.
X 1
Third and fourth characters of Firmware
Version
30196
ASCII String
16-Bit
Battery Cabinet 2 Firmware Version
ex. 0000
15
FW Ver.
X 1
Last two characters of Firmware Version
30197
Unsigned Integer
16-Bit
Battery Cabinet 2 Charger Current
Amps
X 0.01
30198
Unsigned Integer
16-Bit
Battery cabinet 2 Charger Voltage
Volts
x 0.1
30199
Signed Integer
16-Bit
Battery Cabinet 2 Ambient
Temperature
°C
X 1
30200
Signed Integer
16-Bit
Battery Cabinet 2 Ambient
Temperature
°F
x 1
EMD
30201
Signed Integer
16-Bit
Temperature in Celsius
°C
X 1
Note: "-1" means disabled or not
connected
30202
Signed Integer
16-Bit
Temperature Fahrenheit
°F
X 1
Note: "-1" means disabled or not
connected
30203
Signed Integer
16-Bit
Humidity
%
X 1
Note: "-1" means disabled or not
connected