Operating Instructions
59
In order to load version 3.1.0.0 or later software the MP4000 controller needs to have 3.0.0.0 software
installed first.
Load to SD Card file contains both 3.0.0.0 and 3.1.0.0 or later software.
Figure 26: Load Software to SD Card
If controller has 3.0.0.0 software installed, insert SD card to load 3.1.0.0 or later software.
If controller has 2.5.4.0 or older software, insert SD to load 3.0.0.0 software. Removed SD card and wait
for to unit shut down, restart, and auto configuration is completed. Then reinsert SD card to load 3.1.0.0
or later software.
Emergency Run Mode
Use this procedure run the unit in emergency mode if the Control Module (CM) or Power Module (PM)
are found to be defective while under load and no replacement parts are available.
Rotation Check
1. Unplug unit and turn OFF the main circuit breaker (CB) located in the controller box.
2. Remove the compressor wires CP1, CP2, and CP3 from J5 on the PM and connect them to the output
side (left side) of the main CB. Figure 28 on page 60.
3. Make up 3 16 GA (2 mm) jumper wires 16” long (400 mm), mark them CF1, CF2, CF3. Connect the
wires from J11 terminal on the PM and connect the other end to the input (left side) of the compressor
contactor. Be sure to maintain the wiring 1-1, 2-2, 3-3. See Figure 28 on page 60.
1.
3 CF Wires 16 GA 16 in. Long (400 mm)
2.
3 Wires 18 GA 3 in.Long (75 mm)
Figure 27: Make Jumper Wires
1
2
Summary of Contents for 098203
Page 2: ......
Page 3: ...MAGNUM TK 60275 4 MM Rev 3 08 15 Copyright 2012 Ingersoll Rand EMEIA Printed in Ireland...
Page 193: ...Refrigeration Maintenance 191 Figure 163 Filter Drier...
Page 200: ...Refrigeration Maintenance 198 Figure 169 Receiver Tank Figure 170 Water Cooled Condenser Tank...
Page 257: ...255 Schematic Diagram RELEASED 19 Sep 2013...
Page 258: ...256 Wiring Diagram Page 1 of 2 RELEASED 19 Sep 2013...
Page 259: ...257 Wiring Diagram Page 2 of 2 RELEASED 19 Sep 2013...
Page 263: ......