Operating Theory
140
Figure 111: Calibrate Probes
The controller displays [COOR] in place of a temperature offset until the sensor comes within 0.3 C (0.5
F) above or below 0 C (32 F).
The controller displays the actual temperature offset when the sensor temperature is within 0.3 C (0.5 F)
above or below 0 C (32 F).
NOTE: The sensors should be in the ice bath a total of 15 minutes or more to assure the sensor
temperature has bottomed out.
8. Press the
F3
key to release the current actual temperature offsets from the controller memory.
Observe the sensor temperatures in the [CORR] row.
9. Press the
F4
ENTER
KEY
to accept the new temperature offsets when all sensor offsets read b
0.3 C (+0.5 F) and - 0.3 C (-0.5) and have been stable for 5 minutes. The controller display will show
the new offsets in the [RESULT] row.
10. Press the
F1
key to exit the Calibrate menu.
Starting Cold Treatment
1. Go to the Setpoint/Control and enter Cold Treatment (CT).
2. Display will show the Cold Treatment setting list, scroll up and down to edit and enter the settings per
the load specifications.
NOTE: Once Cold Treatment has been started, it must be stopped to change any of the settings.
Figure 112: Starting CT
3. Select EXIT. The Standard Display will appear showing “CT In Progress”. CT is activated and the trip
begins.
Summary of Contents for 098203
Page 2: ......
Page 3: ...MAGNUM TK 60275 4 MM Rev 3 08 15 Copyright 2012 Ingersoll Rand EMEIA Printed in Ireland...
Page 193: ...Refrigeration Maintenance 191 Figure 163 Filter Drier...
Page 200: ...Refrigeration Maintenance 198 Figure 169 Receiver Tank Figure 170 Water Cooled Condenser Tank...
Page 257: ...255 Schematic Diagram RELEASED 19 Sep 2013...
Page 258: ...256 Wiring Diagram Page 1 of 2 RELEASED 19 Sep 2013...
Page 259: ...257 Wiring Diagram Page 2 of 2 RELEASED 19 Sep 2013...
Page 263: ......