Main Menu
124
NOTE: If the inlet / outlet tubes or filter need to be cleared, disconnect from the gas analyzer
BEFORE purging air through the tubes. If tubes remain connected, serious damage to the gas
analyzer could occur.
Data Menu
Display Indication
Corrective Action(s)
CO2%
Open or Short
If no alarm has been generated, the
system most likely has not
communicated with or is verifying
communications with the analyzer.
Follow action for ‘Stale Atmosphere’
steps noted above. If fault exists, an
alarm will be generated.
O2%
Open or Short
If no alarm has been generated, the
system most likely has not
communicated with or is verifying
communications with the analyzer.
Follow action for ‘Stale Atmosphere’
steps noted above. If fault exists, an
alarm will be generated.