Specifications
19
Normal R-404A System Operating Pressures (Scroll Compressor)
Container Temp.
Operating
Mode
Ambient
Temp.
Suction Pressure
Discharge Pressure
21 C (70 F)
Cool
27 to 38 C, 80
to 100 F
410 to 670 kPa, 4.10 to 6.70
bar, 59 to 97 psig
2140 to 2650 kPa, 21.40 to
26.50 bar, 310 to 385 psig
16 to 27 C, 60
to 80 F
400 to 600 kPa, 4.00 to 6.00
bar, 58 to 87 psig
1725 to 2140 kPa, 17.25 to
21.40 bar, 250 to 310 psig
2 C (35 F)
Cool
27 to 38 C, 80
to 100 F
385 to 425 kPa, 3.85 to 4.25
bar, 56 to 62 psig
1860 to 2380 kPa, 18.60 to
23.80 bar, 270 to 345 psig
16 to 27 C, 60
to 80 F
345 to 385 kPa, 3.45 to 3.85
bar, 50 to 56 psig
1450 to 1860 kPa, 14.50 to
18.60 bar, 210 to 270 psig**
-18 C (0 F)
Cool
27 to 38 C, 80
to 100 F
214 to 228 kPa, 2.14 to 2.28
bar, 31 to 33 psig
1515 to 2035 kPa, 15.15 to
20.35 bar, 220 to 295 psig**
16 to 27 C, 60
to 80 F
200 to 215 kPa, 2.00 to 2.15
bar, 29 to 31 psig
1100 to 1515 kPa, 11.00 to
15.15 bar, 160 to 220 psig**
-29 C (-20 F)
Cool
27 to 38 C, 80
to 100 F
145 to 160 kPa, 1.45 to 1.60
bar, 21 to 23 psig
1450 to 1965 kPa, 14.50 to
19.65 bar, 210 to 285 psig**
16 to 27 C, 60
to 80 F
130 to 145 kPa, 1.30 to 1.45
bar, 19 to 21 psig
1035 to 1450 kPa, 10.35 to
14.50 bar, 150 to 210 psig**
Suction and discharge pressures vary too greatly during Modulation Cool to use for evaluating or diagnosing refrigeration
system performance. During the Modulation Cool mode, the suction pressure will vary between 100 and 450 kPa, 1.0 and 4.5
bar, 15 and 65 psig depending upon the percent (percent) cooling capacity.
**Discharge pressure is determined by condenser fan cycling.
MP-4000 Controller Specifications
Temperature Controller:
Type
MP-4000 is a controller module for the Thermo King
Unit. Additional requirements can be met by means of expansion
modules. The MP4000 is solely responsible for temperature
regulation of the reefer container, but other monitoring equipment
can be used in conjunction with the MP 4000 - such as a chart
recorder.
Setpoint Range
-40.0 to +30.0 C (-31.0 to +86.0 F)
Digital Temperature Display
-60.0 to +80.0 C (-76.0 to +176.0 F)
Controller Software (Original Equipment):
Version
See controller identification decal
Defrost Initiation:
Evaporator Coil Sensor
•
Manual Switch or Demand Defrost Initiation:
Coil must be
below 18 C (65 F). Defrost cycle starts when technician or
controller requests defrost initiation.
•
Timed Defrost Initiation:
Coil must be below 4 C (41 F). Defrost
cycle starts 1 minute after the hour immediately following a
defrost timer request for defrost initiation. For example, if the
defrost timer requests a defrost cycle at 7:35, the defrost cycle
will start at 8:01. Datalogger will record a Defrost event for each
interval in which a Defrost cycle is pending or active (i.e. both the
8:00 and 9:00 data logs).
v
Summary of Contents for 098203
Page 2: ......
Page 3: ...MAGNUM TK 60275 4 MM Rev 3 08 15 Copyright 2012 Ingersoll Rand EMEIA Printed in Ireland...
Page 193: ...Refrigeration Maintenance 191 Figure 163 Filter Drier...
Page 200: ...Refrigeration Maintenance 198 Figure 169 Receiver Tank Figure 170 Water Cooled Condenser Tank...
Page 257: ...255 Schematic Diagram RELEASED 19 Sep 2013...
Page 258: ...256 Wiring Diagram Page 1 of 2 RELEASED 19 Sep 2013...
Page 259: ...257 Wiring Diagram Page 2 of 2 RELEASED 19 Sep 2013...
Page 263: ......