Diagnosis: Troubleshooting, Warnings and Alarm Codes
215
20
Low Voltage On Line – Unit Stopped
• When:
• Low voltage observed, voltage has been
below 330 VAC and has not risen above
340VAC yet.
• After 30 minutes this warning will set the low
voltage alarm.
• Indicates:
• Poor quality of power source.
• Enter Manual Function Test menu and test
(operate) components to load the power source.
Check volts and amps to help determine the
problem.
21
Current Too High – Check Compressor and
Fans
• When:
• When the component current draw exceeds
expected. 50% above expected amps for 4
minutes.
• Indicates:
• Digital Control valve malfunction.
• Compressor, evaporator fans motor,
condenser fan motor or heater current too
high.
• Defective volt or amp meter on power
module.
• Power supply voltage too low.
• Enter Manual Function Test menu and test
(operate) each component. Check volts and
amps to determine which component has high
amp draw.
• Check power supply volts.
• Check volt and ampere meter.
• When the warning is set the current power
consumption is logged in the event log.
22
Current Too Low – Check Compressor and
Fans
• When:
• When the component current draw exceeds
expected. 50% below expected for 4
minutes.
• Indicates:
• Defective or open high pressure cutout
switch.
• Defective or open motor internal high
temperature protection switch.
• Unit on water-cooled condensing with no
water flow.
• Defective condenser coil sensor or sensor
location.
• Check Display for High Pressure Cutout
message.
• Enter Manual Function Test menu and test
(operate) each component. Check volts and
amps to determine which component has low
amp draw.
• Check volt and ampere meter.
Warnings and Controller Actions (Continued)
Warning
No.
Warning Message/Description
Controller Action/Corrective Action
Summary of Contents for 098203
Page 2: ......
Page 3: ...MAGNUM TK 60275 4 MM Rev 3 08 15 Copyright 2012 Ingersoll Rand EMEIA Printed in Ireland...
Page 193: ...Refrigeration Maintenance 191 Figure 163 Filter Drier...
Page 200: ...Refrigeration Maintenance 198 Figure 169 Receiver Tank Figure 170 Water Cooled Condenser Tank...
Page 257: ...255 Schematic Diagram RELEASED 19 Sep 2013...
Page 258: ...256 Wiring Diagram Page 1 of 2 RELEASED 19 Sep 2013...
Page 259: ...257 Wiring Diagram Page 2 of 2 RELEASED 19 Sep 2013...
Page 263: ......