![Thermo King 098203 Maintenance Manual Download Page 255](http://html1.mh-extra.com/html/thermo-king/098203/098203_maintenance-manual_1104405255.webp)
Diagnosis: Troubleshooting, Warnings and Alarm Codes
253
141
Power Module Heat Exchanger Too Hot
• Occurs if the power module heat exchanger
temperature gets above 105C.
• Since activating the heating element is the far
most heat applying solid state switch, activating
is bypassed to reduce temperature.
• Indicates:
• Poor cooling to the back side of the control box.
• Check for blocked air flow to the back side of
the control box.
• Ambient temperature might just be high.
157
Data Logger Battery Failure
Firmware version 3.3.0 or newer:
• Occurs if the battery is connected and the battery
protection circuit is activated as a result of
over-current, over-charge or over-discharge.
• Battery voltage must stay below 2.5V after the
battery has been charged for 3 minutes.
• Check the battery physically, dismount and
examine wires and the connection to the
controller.
• Replace battery.
Alarm Codes, Descriptions and Corrective Actions (Continued)
Code
Description
Corrective Action
Summary of Contents for 098203
Page 2: ......
Page 3: ...MAGNUM TK 60275 4 MM Rev 3 08 15 Copyright 2012 Ingersoll Rand EMEIA Printed in Ireland...
Page 193: ...Refrigeration Maintenance 191 Figure 163 Filter Drier...
Page 200: ...Refrigeration Maintenance 198 Figure 169 Receiver Tank Figure 170 Water Cooled Condenser Tank...
Page 257: ...255 Schematic Diagram RELEASED 19 Sep 2013...
Page 258: ...256 Wiring Diagram Page 1 of 2 RELEASED 19 Sep 2013...
Page 259: ...257 Wiring Diagram Page 2 of 2 RELEASED 19 Sep 2013...
Page 263: ......