Operating Instructions
55
Unit On/Off Key
•
ON.
Unit will operate on Cool or Heat depending on the controller setpoint
temperature and the container air temperature.
•
OFF.
The unit will not operate.
Sequence Of Operation
Unit Start-up
Connect unit to 460 Volt shore power or genset.
Turn circuit breaker on at post to apply power to unit.
•
Display will show date and software revision
Press and Hold ON/OFF key for 2 seconds
•
Display shows RA, SA, SP
•
PM 4000 Setup
•
Power Module Init
•
Power Module Phase test - Shows heater icon
•
Power module Ready
•
Stop Plant
Unit starts and shows CHILLED COOLING
and shows mode of operation
.
NOTE: Random time delays during the initial unit start-up minimize peak current draw.
Initiating a Manual Defrost
Turn the
U
NIT
O
N
. Allow Unit to start and stabilize.
Complete the following steps:
1. Press the
D
EFROST
Special Function key.
• If the unit operating conditions allow a manual
defrost (e.g. evaporator coil temperature is less than
18 C [56 F]), the unit enters Defrost.
2. The defrost cycle automatically terminates and
returns the unit to normal operation.
Summary of Contents for 098203
Page 2: ......
Page 3: ...MAGNUM TK 60275 4 MM Rev 3 08 15 Copyright 2012 Ingersoll Rand EMEIA Printed in Ireland...
Page 193: ...Refrigeration Maintenance 191 Figure 163 Filter Drier...
Page 200: ...Refrigeration Maintenance 198 Figure 169 Receiver Tank Figure 170 Water Cooled Condenser Tank...
Page 257: ...255 Schematic Diagram RELEASED 19 Sep 2013...
Page 258: ...256 Wiring Diagram Page 1 of 2 RELEASED 19 Sep 2013...
Page 259: ...257 Wiring Diagram Page 2 of 2 RELEASED 19 Sep 2013...
Page 263: ......