Controller Description
41
Glossary of Mode Descriptions
Chilled/Cooling
Chilled cooling is a mode where the Unit setpoint is set to above -10C. The function here is to maintain
setpoint temperature by controlling the temperature on the supply air.
The supply air is not allowed to be lower than the setpoint. Chilled/cooling mode can operate the unit in
different modes where the compressor can run loaded, unloaded/loaded and vapor injection depending on
the need for cooling capacity. The condenser fan will operate in an on/off algoritim depending on the
temperature on the condenser. The evaporator fans will operate in either high or low speed mode
depending on the need for capacity.
- Compressor On Unloaded
- Compressor On loaded without Vapour Injection
- Compressor On loaded with Vapour Injection
- SmartPTI has recently been running and no problems found
- Controlling mode optimized
- Controlling mode economy
- Bluetooth
- Cell Phone
- GPS Signal
- RMM
- Battery Full (Datalogger Battery)
- Battery Charging (Datalogger Battery)
- Battery state not known. Temperature to low or high, charger suspended. (Datalogger Battery)
- Battery Error (Datalogger Battery)
Glossary of Symbols (Continued)
Summary of Contents for 098203
Page 2: ......
Page 3: ...MAGNUM TK 60275 4 MM Rev 3 08 15 Copyright 2012 Ingersoll Rand EMEIA Printed in Ireland...
Page 193: ...Refrigeration Maintenance 191 Figure 163 Filter Drier...
Page 200: ...Refrigeration Maintenance 198 Figure 169 Receiver Tank Figure 170 Water Cooled Condenser Tank...
Page 257: ...255 Schematic Diagram RELEASED 19 Sep 2013...
Page 258: ...256 Wiring Diagram Page 1 of 2 RELEASED 19 Sep 2013...
Page 259: ...257 Wiring Diagram Page 2 of 2 RELEASED 19 Sep 2013...
Page 263: ......