Refrigeration Maintenance
179
Purge High Side to Low Side
1. Attach gauge manifold set (see “Gauge Manifold Set Attachment and Purging” for proper procedure
for connecting to compressor).
2. Close both hand valves on the gauge manifold (front seated).
3. Connect charging hose to a source of nitrogen. Adjust pressure regulator to the proper pressure for the
required procedure.
4. Purge system high side to low side.
Maximum Gas Pressures
The following procedures should utilize the following
maximum
gas pressure:
•
Leak Testing: 1034 to 1200 kPa, 10.34 to 12.00 bar, 150-174 psig,
•
Purging/Dehydration: 69 to 138 kPa, 0.69 to 1.38 bar, 10-20 psig,
•
Soldering: 35 kPa, 0.35 bar, 5 psig.