Main Menu
97
Display*
LED
Display
Description
Possible
Alarms
Duration
(Time)
RUNNING PTI
0
°
C / 32
°
F
00:00:00
0.0C 10.0C 10.0C
Supply
temp.
Unit operates in normal mode with 0C
(32F) setpoint for 30 minutes after
previous test is completed. At the end of
30 minutes, “Chill End” temperatures are
recorded in PTI log. Sensor values for
supply, return and evaporator sensors are
recorded in the event log.
None
120 minutes
maximum
RUNNING PTI
DEFROST
00:00:00
-18.0C 10.0C 10.0C
Return
temp.
Unit operates in normal mode with -18C
(0F) setpoint and defrost activated. Defrost
terminates when evaporator temperature
increases to 18C (65F).
20
30 minutes
RUNNING PTI
-18
°
C / 0
°
F
00:00:00
-18.0C 10.0C 10.0C
Return
temp.
Unit operates in normal mode with -18C
(0F) setpoint. When return air temperature
decreases to setpoint, Frozen Arrival”
temperatures are recorded in PTI log.
“PTI End” are recorded in PTI log and a
Trip Start is automatically activated.
22, 60
90 minutes
maximum
PTI PASS – PRESS
KEY
Return
temp.
Unit will remain OFF until any key is
pressed.
If alarms occurred during PTI, Display
shows “PTI FAIL – PRESS KEY”.
None
180 minutes
maximum
* Readings may vary depending on voltage and temperature
Summary of Contents for 098203
Page 2: ......
Page 3: ...MAGNUM TK 60275 4 MM Rev 3 08 15 Copyright 2012 Ingersoll Rand EMEIA Printed in Ireland...
Page 193: ...Refrigeration Maintenance 191 Figure 163 Filter Drier...
Page 200: ...Refrigeration Maintenance 198 Figure 169 Receiver Tank Figure 170 Water Cooled Condenser Tank...
Page 257: ...255 Schematic Diagram RELEASED 19 Sep 2013...
Page 258: ...256 Wiring Diagram Page 1 of 2 RELEASED 19 Sep 2013...
Page 259: ...257 Wiring Diagram Page 2 of 2 RELEASED 19 Sep 2013...
Page 263: ......