Operating Theory
129
A.
Cool with Modulation (control temperature
differential is above setpoint)
B.
Heat (electric heaters pulse on and off on a 60
second duty cycle if the control temperature
differential is below setpoint.)
C.
In-range (based on supply air temperature)
1.
Decreasing Temperature
2.
Setpoint
3.
Increasing Temperature
Chill Load Control Sequence (Setpoints at -9.9 C [14.1 F] and Above)