EM330D User Manual
A Special Purpose Inverter for Hoisting
96
9.2.9
Inverter Stops Output While Motor Runs
Insufficient DC brake at stop
DC brake torque at stop is too small. Please increase setting value of DC brake
current at stop (F3-25).
DC braking time at stop is too short. Please increase setting value of stop DC
brake time (F3-27). Generally, please increase the DC brake current at stop
first.
9.2.10
Output Frequency Does Not Output as per the Setting Frequency
The setting frequency is within the range of skip frequency
The function of skip frequency is to forbid the inverter to output within the skip
frequency range. Please check if the skip frequency of F6-16~F6-21and its range
are proper.
Setting frequency exceeds the upper limit frequency
When the setting frequency exceeds the setting value of upper limit frequency,
output frequency outputs as per the upper limit frequency. Reset the setting
frequency to make it within the range of upper limit frequency, or check whether
F0-16 and F0-17 are proper.