EM330D User Manual
A Special Purpose Inverter for Hoisting
72
Reach(Enabled at Running)
by F0-18, the output terminal is on. (The output terminal will be
off when accelerating to the lower limit frequency at the initial
running. When the output frequency exceeds the lower limit
frequency at the first time, and then reaches lower limit frequency
again, the output terminal is on.)
12~16
Not Used
17
Overload Alarming Output
Not apply to hoisting
18
Overvoltage Stall
19
Current Limit
20
Frequency Zero Speed
Detection(Output Frequency
Detection)
21
Not Used
22
Motor 2 Enabled
23
Setting running time is up
24
Brake control
The terminal has brake control logic function and can control the
power supply of brake via intermediate relay.
25
Not Used
26
Inverter is ready for running
When inverter is power-on normally and no fault occurs, the
output terminal is on.
27
Brake detection remind output
1.
When connecting to the buzzer and when the setting Brake
detection timelag is up, the terminal will remind Brake
detection automatically.
2.
The output of this terminal can be reset through fault reset
terminal or by the RESET key on the keypad. When
repowered-on, it will remind automatically.
3.
Only after Brake detection passed, Brake detection remind
time will be counted from 0.
28~32
Not Used
No.
Function
Range
Unit
Default
Type
F2-16
Analog Output Terminal M0
See Table 6-3
Analog Output Full Scale
6
●
F2-17
Analog Output Terminal M1
6
●
EM330D provides 2 programmable analog output terminals: M0 and M1 which can output
0
~
10V voltage signal or 0-20mA current signal by jump line selection.
No.
Function
Range
Unit
Default
Type
F2-22
M0 Output Lower Limit
0.00
~
100.00
%
0.00
●
F2-23
M0 Output Upper Limit
0.00
~
100.00
%
100.00
●
F2-24
M0 Output Gain
0.00
~
300.00
%
300.00
●