In JOG running mode, inverter runs at the frequency set by F0-11, the
acceleration/deceleration time taken for running to Fmax is set by F0-12/F0-13.
★
Jog acceleration time is the time taken for the output frequency to rise from 0Hz up to
maximum frequency Fmax. Deceleration time is the time taken for the output frequency
to drop from Fmax down to 0Hz.
★
In jog running mode, keep pressing the JOG button or terminal JOG is on. Otherwise, it
will be considered as the jog command cancelled.
Note that the unit of acceleration /deceleration time is second or minute, defined by
F3-21.
No.
Function
Range
Unit
Default
Type
F0-14
Carrier Frequency
0kW
~
9kW: 1.000
~
16.000 kHz
11kW
~
37kW: 1.000
~
8.000 kHz
45kW
~
110kW: 1.000
~
4.000 kHz
132kW
~
400kW: 1.000
~
3.000 kHz
kHz
1.000
●
Increasing carrier frequency could reduce motor noise, but it will result in inverter heating
up. When carrier frequency is higher than the default, the rated power of inverter should
decrese 5% as each increment of 1 kHz carrier frequency.
Correlation between motor rated power and carrier frequency is suggested as following:
Motor Rated Power Pe
≤15kW
≤30kW
≤75kW
≤132kW
>
132KW
Carrier Frequency F
c
≤10.0kHz
≤8.0kHz
≤6.0kHz ≤4.0kHz
≤2.5kHz
The setting range of carrier frequency is limited by power rating:
0kW
~
9kW: carrier frequency range 1.000
~
16.000 kHz
11kW
~
37kW: carrier frequency range 1.000
~
8.000 kHz
45kW
~
110kW: carrier frequency range 1.000
~
4.000 kHz
132kW
~
400kW: carrier frequency range 1.000
~
3.000 kHz
No.
Function
Range
Unit
Default
Type
F0-16
Maximum Frequency
Fmax: 20.00
~
600.00
Hz
50.00
〇
F0-17
Upper Limit Frequency Fup: Fdown
~
Fmax
Hz
50.00
〇
F0-18
Lower Limit Frequency
Fdown: 0.00
~
Fup
Hz
0.00
〇
F0-16
Fmax indicates the maximum setting frequency permitted by inverter. Range of
Fmax: 20.00-600.00Hz.
F0-17
Fup indicates the maximum permitted running frequency after inverter start-up.
Range of Fup: Fdown~Fmax.
No.
Function
Range
Unit
Default
Type
F0-11
Jog Numeric Frequency
0.00
~
Fmax
Hz
5.00
●