EM330D User Manual
A Special Purpose Inverter for Hoisting
58
Fb-00
Frequency (Running Up) for disengaging the
external brake
3.00 Hz
Fb-01
Frequency (Running Down) for disengaging the
external brake
3.00 Hz
Fb-02
Delay time before the external brake is
disengaged
0.3S
Fb-03 Delay time after the external brake is disengaged
0.3S
Fb-04
Frequency (Running Up) for engaging the
external brake
3.00 Hz
Fb-05 Delay time before the external brake is engaged
0.2S
Fb-06
Delay time after the external brake is engaged at
running up
0.3S
Fb-07
Current abnormity identifying time for
disengaging the external brake
5.0S
Fb-08
Delay time after the external brake is engaged at
running down
0.3S
Fb-11
Frequency (Running Down) for engaging the
external brake
2.50 Hz
Fb-27
Brake Disengage Conditions
Enabled when frequency and
current reached simultaneously
1
Fb-28
Brake Disengage Current
10.00%
~
150.00%
60.00%
FC-07 Current Limit Control
Current limit disabled
0
FC-16 Brake Duty Ratio
100.00%
100.00%
FC-18 AVR
AVR enabled
001
FC-19 Overvoltage control selection
Overvoltage stall prohibited, and
dynamic brake enabled
0010
FC-28 Disabled Trips 1
Disable input phase loss and stable
overcurrent trips
01010000
FE-17 X1 Off Delay
0.0S
FE-18 X2 Off Delay
0.0S
Remarks:
1.
Defaults of F4-28=9 Application Macros for Construction Lift as shown in the
table above.
2.
Users can define the range of those parameters based on real needs if the defaults
may not meet the application needs.