EM330D User Manual
A Special Purpose Inverter for Hoisting
48
F9-24 Start-up Delay
0.00
~
10.00
(The time for inverter to wait for
the initial operation after
power-on)
S
3.00
●
F9-25 Terminal Operation Command Control
0: Terminal shall be off first, and
then on.
1: Terminal shall not be off,
inverter will run directly.
0
〇
F9-26
~
F9-29
Not Used
F9-30 Undervoltage Detection Scaling
0.00
~
100.00(Udc_e)
%
65.18
〇
F9-31 Undervoltage Detection Time
0.00
~
30.00
S
0.50
〇
6.2.9
Group Fb: Parameters of Hoisting Function
No.
Function
Range
Unit
Default Type
Fb-00
Frequency (Running Up) for disengaging the
external brake
0.00
~
20.00
Hz
3.00
〇
Fb-01
Frequency (Running Down) for disengaging the
external brake
0.00
~
20.00
Hz
3.00
〇
Fb-02
Delay time before the external brake is
disengaged
0.0
~
10.0
S
0.3
〇
Fb-03
Delay time after the external brake is
disengaged at running up
0.0
~
10.0
S
0.3
〇
Fb-04
Frequency (Running Up) for engaging the
external brake
0.00
~
20.00
Hz
3.00
〇
Fb-05 Delay time before the external brake is engaged 0.0
~
10.0
S
0.2
〇
Fb-06 Delay time after the external brake is engaged 0.0
~
10.0
S
0.5
〇
Fb-07
Current abnormity identifying time for
disengaging the external brake
0.0
~
10.0
S
2.0
〇
Fb-08
Delay time after the external brake is engaged
at running down
0.0
~
10.0
S
0.3
〇
Fb-09
~
Fb-10
Not Used
Fb-11
Frequency (Running Down) for engaging the
external brake
0.00
~
20.00
Hz
2.50
〇
Fb-12
~
Fb-26
Not Used
Fb-27
Enabling conditions for disengaging the
external brake
0:
Enabled
when
frequency reached
1
〇