EM330D User Manual
A Special Purpose Inverter for Hoisting
82
Fb-04
Frequency (Running Up) for engaging the external
brake
0.00
~
20.00
Hz
3.00
〇
Fb-05
Delay time before the external brake is engaged
0.0
~
10.0
S
0.2
〇
Fb-06
Delay time after the external brake is engaged
0.0
~
10.0
S
0.5
〇
Fb-07
Current abnormity identifying time for disengaging
the external brake
0.0
~
10.0
S
2.0
〇
Fb-08
Delay time after the external brake is engaged at
running down
0.0
~
10.0
S
0.3
〇
Fb-00
Frequency (Running Up) for disengaging the
external brake
0.00
~
20.00
Hz
2.50
〇
See Figure 7-12 for brake sequence logic.
f1:Fb-00 Frequency (Running Up) for disengaging the external brake
f3:Fb-04 Frequency (Running Up) for engaging the external brake
t1:Fb-02 Delay time before the external brake is disengaged
t2:Fb-03 Delay time after the external brake is disengaged at running up
t3:Fb-05 Delay time before the external brake is engaged
t4:Fb-06 Delay time after the external brake is engaged
I1:Fb-28 Current for disengaging the external brake
t4
t2
f1
f3
f2
t3
OFF
ON
ON
OFF
ON
Up CMD
Output Frequency
Brake Control
0Hz
Output Current
A1
t1
Figure 7-12 Brake Sequence Logic of Running Up
The brake sequence logic of running down is similar as that of running up. The
comfortablility can be adjusted via f3, t3 and t4.
Fb-07: C
urrent abnormity identifying time for disengaging the external brake
If output frequency reached and output current does not reach the disengaging current of
brake, and when the setting time of Fb-07 is up, inverter will trip EXT(External fault).
Please check whether motor is well connected or not.