EM330D User Manual
A Special Purpose Inverter for Hoisting
66
1. When reverse is permitted, inverter will judge present running direction based
on the setting of F0-08 and the status of terminal F/R. If F0-08=1 and terminal F/R
is on, inverter runs forward.
2. If the setting forward direction of inverter is not identical with the expected running
direction of motor, please switch any two of output cables (U, V, and W) of inverter or set
F0-08=1.
F0-26=0
Primary speed setting mode is regular speed setting mode. Primary numeric
speed setting mode or analog signal setting mode can be set by selecting parameter of
F0-06.
F0-26=1/2 Not used
No.
Function
Range
Unit
Default
Type
F0-27
Menu Mode Options
0
:
Basic Menu Mode
1
:
Advanced Menu Mode
1
〇
F0-27=0
Keypad only displays the basic setting parameters of F0~F5.
(These 6-group parameters could meet the needs of most of applications.)
F0-27=1
Keypad displays 16-group parameters of F0~FE.
No.
Function
Range
Unit
Default
Type
F0-28
Default Control
0: Disabled
1: Defaults reset
0
〇
F0-29
Parameter Setting Control
0: Parameter set permitted
1: Parameter lock 0
2: Parameter lock 1
0
〇
Reset Default
F0-28=1 Reset Default:
Except motor parameters in Group F1 and FA, inverter parameter
in Group Fd, the other parameters will reset to default. After reset completed, F0-28=0
automatically.
Parameter Lock
F0-29=0
All parameters are permitted to be edited.
F0-29=1Parameter lock 0
: Lock parameters except numeric settings. The numeric settings
are primary numeric frequency setting F0-07, auxiliary numeric frequency setting F9-06,
jog running frequency F0-11, preset speed 1~15(F3-00
~
F3-14), numeric torque current
F5-12.
F0-29=2 Parameter locked 1:
Lock all parameters except F0-29, inverter will remain the
setting before unlocked.
No.
Function
Range
Unit
Default Type
F0-26
Primary Speed Setting Mode
0:Regular Speed Setting Mode
1~2
:
Not used
0
〇