EM330D User Manual
A Special Purpose Inverter for Hoisting
73
F2-25
M1 Output Lower Limit
0.00
~
100.00
%
0.00
●
F2-26
M1 Output Upper Limit
0.00
~
100.00
%
100.00
●
F2-27
M1 Output Gain
0.00
~
300.00
%
300.00
●
Upper limit/lower limit of analog output can be set to meet different requirements.
Final analog output signal=Output gain*analog output
Analog output gain and its upper/lower limit F2-22~F2-27 are for terminal M0 and M1, and
irrelevant to the current running status.
1.
In order to meet different needs, the actual full scale voltage of M0/M1 is
10.9V, and the actual full scale current is 22mA.
2.
Default of M0 and M1 is 0
~
10V.
3.
If there is high demand for accuracy of analog output in application, check idling
output of M0 and M1 with multimeter.
7.4
Group F3: Preset Speed Parameters
No.
Function
Range
Unit
Default
Type
F3-00
Preset Speed 1
0.00
~
Fmax
Hz
50.00
●
F3-01
Preset Speed 2
0.00
~
Fmax
Hz
5.00
●
F3-02
Preset Speed 3
0.00
~
Fmax
Hz
10.00
●
F3-03
Preset Speed 4
0.00
~
Fmax
Hz
15.00
●
F3-04
Preset Speed 5
0.00
~
Fmax
Hz
20.00
●
F3-05
Preset Speed 6
0.00
~
Fmax
Hz
25.00
●
F3-06
Preset Speed 7
0.00
~
Fmax
Hz
30.00
●
F3-07
Preset Speed 8
0.00
~
Fmax
Hz
35.00
●
F3-08
Preset Speed 9
0.00
~
Fmax
Hz
40.00
●
F3-09
Preset Speed 10
0.00
~
Fmax
Hz
45.00
●
F3-10
Preset Speed 11
0.00
~
Fmax
Hz
50.00
●
F3-11
Preset Speed 12
0.00
~
Fmax
Hz
50.00
●
F3-12
Preset Speed 13
0.00
~
Fmax
Hz
50.00
●
F3-13
Preset Speed 14
0.00
~
Fmax
Hz
50.00
●
F3-14
Preset Speed 15
0.00
~
Fmax
Hz
50.00
●
Through preset speed control terminals and 15 preset frequency commands,
EM330D can
provide 16 preset speeds by combining keypad numeric setting mode and analog setting
mode. Furthermore, it can be adjusted at any time through repeated addition analog input.
Setting Preset Speed Terminals
Terminal
No.
Default
Function
X3
F2-02
3
Preset Speed Terminal 1
X4
F2-03
4
Preset Speed Terminal 2
X5
F2-04
5
Preset Speed Terminal 3
X6
F2-05
6
Preset Speed Terminal 4
X7
F2-06
10
Inverter Fault Reset