User Manual of A90 Series Inverter
114
Chapter 7
Function Code Details
7.1
Basic Function Parameter Group of F00 Group
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F00.01
Drive control
mode of motor 1
0: V/F control (VVF)
1: Speed sensorless vector control
(SVC)
0
○
F00.01=0: V/F control (VVF)
It is used for one-to-many, fast and low-precision speed control.
F00.01=1: speed sensorless vector control (SVC)
The open-loop vector control is suitable for general high-performance control. An
inverter drives one motor only of the loads, e.g. machine tools, centrifuges, drawing
machines, and injection molding machines.
1. In order to improve the control performance, self-learning is needed to
obtain the correct motor parameters before vector control.
2. In the vector control mode, the inverter can be used with one motor only,
and the motor capacity should not be greatly different from the inverter capacity;
otherwise, the control performance may decline or the system may not work properly.
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F00.02
Options of
command
source
0: keyboard control (LOC/REM
indicator: ON)
1: terminal control (LOC/REM
indicator: OFF)
2: communication control
(LOC/REM indicator: flicker)
0
○
F00.02=0: keyboard control (LOC/REM indicator ON)
The start and stop of the inverter are controlled by the RUN key
RUN
, STOP key
STOP
RESET
and multi-function key
M.K
on the keyboard. In the case of no fault, press the
multi-function key
M.K
to enter the jog running status, and the RUN key
RUN
to
enter the running status. If the green LED indicator above the RUN key
RUN
is normally