User Manual of A90 Series Inverter
135
F01.20
d-axis
inductance of
synchronous
motor
0.01 ~ 600.00 (rated power of
motor: ≤ 75 kW)
0.001 ~ 60.000 (rated power of
motor: > 75 kW)
mH
Depending
on the
motor type
○
F01.21
q-axis
inductance of
synchronous
motor
0.01 ~ 600.00 (rated power of
motor: ≤ 75 kW)
0.001~ 60.000 (rated power of
motor: > 75 kW)
mH
Depending
on the
motor type
○
F01.22
Counter
electromotive
force of
synchronous
motor
10.0~2,000.0 (counter electromotive
force of rated speed)
V
Depending
on the
motor type
○
F01.23
Initial
electrical angle
of synchronous
motor
0.0~359.9 (valid for synchronous
motor)
0.0
○
The function codes F01.19 to F01.23 are the parameters of the synchronous motor. They
are usually unavailable to users. Please get them through motor parameter
self-identification (F01.34).
Before the motor parameter self-identification, be sure to set F01.00 to F01.08
correctly according to the actual situation. In particular, select the motor type (F01.00=2)
correctly.
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F01.34
Motor parameter
self-learning
0: No operation
1: static self-learning of
asynchronous motor
2: rotation self-learning of
asynchronous motor
11: static self-learning of
synchronous motor
12: rotary self-learning of
synchronous motor
0
○
F01.34=0
: not identified
F01.34=1
: the asynchronous motor remains stationary during parameter
self-identification.
Prior to the static self-learning of the asynchronous motor, please set the motor type